SUB instruction block: Source A Tank_Full, Source B Used, Dest Remaining


SUB (Subtract) writes Source A minus Source B to Dest every scan its rung is true. It is an output instruction with no state and no status bits. Use SUB for a remaining quantity, an error between setpoint and measurement, or an offset removed from a raw reading. Do not use SUB to count down; an ungated SUB Left 1 Left subtracts one every scan. Use CTD for events, or gate the SUB with an ONS.


Operand Type Format Valid Range Required Description
Source A Any numeric tag, member, element or bit, or a literal Tag, Tag.Member, Tag[n], Tag.bit, or a literal Any resolvable numeric reference Yes The value subtracted from.
Source B Same as Source A Same Any resolvable numeric reference Yes The value subtracted.
Dest A writable numeric tag, member or element Tag, Tag.Member, Tag[n] SINT, INT, DINT or REAL; not a literal, not an input pin Yes Where the difference is written.

Literals may be whole numbers (25, -3, 0x1F) or decimals (72.5). A BOOL source reads as 0 or 1. Dest may be the same tag as a source.

Dest type. A whole-number Dest truncates a fractional result toward zero and wraps silently past its range (INT ±32767, DINT ±2,147,483,647); a REAL keeps the fraction. Every type is signed, so a result below zero is stored as a negative number, never clamped.


Nothing. Dest keeps its power-up value.

The instruction does nothing. Dest holds its last value.

Both sources are read, Source B is subtracted from Source A and the result is written to Dest, every scan the rung is true.

Nothing.


Scenario: A day tank holds 500 litres when full. A flow meter accumulates what has been drawn off, and the operator display shows what is left.

Tags:

  • Update — Recalculate, BOOL
  • Tank_Full — Full capacity in litres, INT
  • Used — Litres drawn, INT
  • Remaining — Litres left, INT

Rung 1:

—] [Update———[SUB Tank_Full Used Remaining]———

Scan 1 — Update = 0. Tank_Full reads 500 and Used reads 135. The rung is false, so Remaining still shows 0.

Figure 1 — SUB rung false: Tank_Full 500, Used 135, Remaining 0, rung dark

Scan 2 — Update = 1. 500 − 135 is written: Remaining reads 365.

Figure 2 — SUB rung true: Remaining reads 365, rung lit

If Used ever exceeds Tank_Full, Remaining goes negative. Test for that with LES if the display should clamp at zero.


  • ADD — Add
  • NEG — Negate (0 − Source in one operand)
  • ABS — Absolute Value (the size of a difference regardless of sign)
  • CPT — Compute
  • Compute Instructions — Category index

Control error. SUB Setpoint Measured Error is the classic use. Follow it with ABS when only the size of the error matters, or use LIM on Error for a deadband.

Counting down. SUB Left 1 Left behind an ONS decrements once per event. Without the ONS it runs every scan.

The block never colours. Watch the rung wire and the Dest value line.